Extension of a sprinkler system to NFPA standard
- Deliverables:
- Project Management
- Construction Management
- Construction Safety Management
- Constructability Reviews
- Cost Control
- Quality Assurance
- Interface Management
- Documentation Management
- Location: Hünfeld
- Period: 2016
- Client: Wella Grundstücks- und Vermögensverwaltungs GmbH & Co. KG
- Sprinkler System: Gottschalk Feuerschutzanlagen GmbH
As part of implementing a fire protection concept for an industrial facility, in 2016 the existing sprinkler system was extended by an area of around 2,000 m². Due to changed user requirements, the areas had to be integrated into the existing system in order to prevent fire spread between the ground and upper floors. The extension was carried out in accordance with NFPA 13 and comprised around 170 sprinklers of type K8 (K115) with a 3/4" connection, an activation temperature of 68°C and a design water density of 10.2 l/(min·m²).